Nominal air flow | up to > 5 500 l/s [20 000 m³/h] |
Admissible differential pressure | up to 10 000 Pa |
Tightness of filter housing acc. to DIN 24 496 | leakage rate < 3 · 10-5 of nominal air flow at Δp = 2 000 Pa |
Dwell time at nominal air flow | 0.25 - 2.50 s |
Air flow velocity | < 0.5 m/s |
Features
Information
While with the filter system CFH classic 100% of the loaded carbon will be changed at one time, the load capacity of the carbon will be used more efficient with the filter system CFH hightec. There, only the first half of the filter bed will be disposed, while the relatively unloaded second half of the filter bed will be changed to the first half. Only the second half of the filter bed will be filled with new carbon.
Any adsorption filter system type CFH will be designed according the special requirements of the single project.
Service & Downloads