  • 4.2 Chilled beam DK-LIG/E, with ventilation function, one-sided discharge

    For room cooling and heating in the commercial sector, trade and industry, for high cooling capacities and simultaneous fresh air supply to improve indoor air quality and humidity control. The secondary air is removed directly from occupied zone. The supply air is discharged on one side, which enables parallel placement to the facade or walls. This chilled beam is designed for integration into suspended ceilings made from metal, gypsum plasterboard, mineral fibres ect., or for downstanding installation.

     

    Data

    Nominal width 300 mm (for flush installation)
    375 mm (downstanding)
    Nominal height 265 mm
    Nominal length 1 200, 1 500, 1 800, 2 100, 2 400, 2 700 and 3 000 mm
    Supply air flow 8 – 25 l/(s•m) [30 – 90 m³/(h•m)]
    Surface finish powder coating to RAL (standard RAL 9010)
    Connection type

    sleeve Rp ½, or calibrated pipe and suitable for push-in fitting, spigot DN 100 – DN 150

    Features

    • Compact unit for fresh air supply as well as for cooling and heating according to DIN EN 15116:
      Cooling capacity up to 620 W/m
      Heating capacity up to 315 W/m
    • Reflow surface for secondary air integrated into the chilled beam; an extra reflow surface is thus no longer required in closed ceiling systems
    • Many design options with various types of screens, wings and connections to suspended ceilings
    • Heat exchanger cleanable from room thanks to easily detachable screen
    • Thanks to low height, suitable for low storeys in new or refurbished Buildings
    • Horizontal air distribution with low velocities in the occupied Zone
    • Low sound power Level
    • Optimum layout made possible by the range of Primary air nozzles available

     