  • 5.2 Ventilation unit (recirculated air) for mixing ventilation LG-UM-M-LB, for horizontal floor mounting

    To ventilate office and administrative buildings that have façades with floo-to-ceiling glazing, Krantz supplies a ventilation unit work- ing with recirculated air and designed for raised floor mounting; this compact unit with high output is able to remove the internal cooling and heating loads resulting from the large glazed area.

     

    Data

    Air volume flow rate 55 – 97 l/s [200 – 350 m3/h] (continuous Control)
    Cooling output
    Supply air temperature
    Chilled water temperature
    700 W
    18.5 °C
    15 / 17 °C
    Heating output
    Supply air temperature
    Hot water temperature
    1 515 W
    35 °C
    50 / 40 °C
    Control voltage for fan speed 10 V DC
    Operating voltage 230 V / 50 Hz
    Total power requirement (design value) 56 VA

     

    Features:

    • Cooling and heating at the facade; unit mounted in raised floor
    • Maximum energy saving thanks to energy-efficient cross-flow fan
    • Recirculated air volume flow rate up to 97 l/s [350 m3/h]
    • Cooling output up to 700 W
    • Low sound power level
    • Ideal in conjunction with a floor-mounted supply air ventilation unit providing a minimum percentage of outdoor air
    • Feet adjustable in height to make up for vertical constructional tolerances
    • Optionally fitted with flexible connection hoses, valves and actuators