• EN
  • 1.1.1. Safe Change Filter Housing with Scanner SCF hightec Triple S

    Krantz HEPA filter systems, type SCF hightec Triple S, are used in bio-safety laboratories class 3 and 4.

    Data

     

    Nominal air flow HEPA filter element (filter class H14) up to 420 l/s [3 000 m³/h]
    Max. Initial pressure drop HEPA filter element (filter class H14) 300 Pa

     

    Futures

    The design considers the applicable rules like:

    • "Laboratory biosafety manual" by World Health Organization (WHO)
    • "Biosafety in Microbiological and Biomedical Laboratories" (BMBL)
    • EN 12 128 "Biotechnology - Laboratories for research, development and analysis containment levels of microbiology laboratories, areas of risk, localities and physical safety requirements"
    • Robust filter housing made from stainless steel
    • 3-seal systems for HEPA filter elements
    • Tightness proof frame for HEPA filter elements
    • Safe change collar (bag-in / bag-out) for filter elements
    • In-situ efficiency measurement with scanner system
    • Decontamination ports
    • Seismic approval (option)

    Service & Downloads