• EN
  • 1.4.2. Re-cleanable Filter Systems M-SCF classic

    Re-cleanable HEPA filter systems will be used for demanding requirements on the filter separation performance (HEPA), high particle concentrations and abrasive dusts.

    Data

    Air flow (adjustable) 840 l/s [3 000 m³/h]
    Admissible differential pressure ± 7 000 Pa
    Admissible design temperature 80°C
    Necessary upstream pressure 6 bar continuous pressure
    Compressed air quality oil- and water - free, dew Point -5 °C
    Conection flange raw gass side DN 350 (Jakob system)

    Tightness of filter housing acc.
    to DIN 24 496

    leakage rate < 3 · 10-5 of nominal air flow at Δp = 2 000 Pa 
    Tightness of filter seat acc.
    to DIN 24 496
    leakage rate < 3 · 10-5 of nominal air flow at Δp = 2 000 Pa 

     

    Features

    • Both blocks form independent units and can be transported independently
    • For simple room air filtering, M-SCF-V alone can be used. For this block, an extensive range of special accessories is available on request, including additional HEPA filter stages, active carbon filter stages, and plug-in sound damper units.
    • To ensure easy decontamination, welded seams on components in contact with the media are free from any gaps and continuously welded.
    • The clamping mechanisms for HEPA filter elements can be operated from outside
    • Contamination-free filter exchange (bag-in-bag-out)

     

    Service & Downloads

    Your contact person

    Marco Sauder

    Deputy Head of Filter and Damper Systems

    T +49 241 441 285

    M +49 173 520 1543

    marco.sauder@krantz.de