• EN
  • 1.4.1. Mobile Re-cleanable Filter Systems RHF hightec

    Re-cleanable HEPA filter systems will be used for demanding requirements on the filter separation performance (HEPA), high particle concentrations and abrasive dusts.

    Data

    Dimensions 1 600 x 1 900 x 790 mm
    Air flow 420 l/s [1 500 m³/h]
    Admissible Operation pressure ± 6 000 Pa
    Admissible design temperature 90°C
    Compressed air cosumption per recleaning approx. 0.4 Nm³/filter element
    Recleaning time per filter element approx. 6 s
    Tightness of filter housing acc. to DIN 24 496 Lekage rate < 3 · 10-5 of nominal air flow at Δp = 2 000 Pa
    Tightness of filter seat acc. to DIN 24 496 Lekage rate < 3 · 10-5 of nominal air flow at Δp = 2 000 Pa

     

    Your benefits:

    • Optional possibility of recycling the purified dusts
    • Low disposal costs
    • No filter element exchange necessary

    Examples of industrial uses:

    • Teardown of nuclear systems
    • Pharmaceutical production processes
    • Battery manufacture

    More features:

    • Top-down principle
    • Lower depths of filter elements for critical dust
    • Very high cleaning pressure (up to 4 bar overpressure in nozzle bar)
    • Patented, reinforced RHF ® standard size elements
    • Pressure loss reduction through cleaning process, i. e.
      • Lower and more constant initial pressure drop after cleaning
      • Higher working pressure drop in filter possible
      • Formation of a filter “cake” on the surface of the filter medium
      • Good separation of agglomerated dust in the hopper
      • Suitable for different kinds of dust, especially for critical particles (rough, sticky, etc.)

    Service & Downloads

    Your contact person

    Marco Sauder

    Deputy Head of Filter and Damper Systems

    T +49 241 441 285

    M +49 173 520 1543

    marco.sauder@krantz.de