• EN
  • 5.4 Induction unit for mixing ventilation IG-M-LB, for horizontal floor mounting

    Induction unit for cooling, heating, and fresh air supply along the building facade, via a raised floor, providing a high level of thermal comfort.

    Data

    Primary air volume flow rate 4 – 36 l/s [15 – 130 m³/h]
    Cooling capacity (total) max. 1 320 W
    Cold water temperature 15 / 17 °C
    Heating capacity max. 1 200 W
    Hot water temperature 50 / 40 °C
    Heating capacity with self-convection 350 W
    Nominal unit width 1 200 mm (available 800, 900, 1 200, 1 350, 1 600 mm)
    Grille depth 380 or 500 mm
    Height 220 mm

    Features:

    • Low pressure loss (70 to 200 Pa), therefore energy-saving operation
    • Low sound power level
    • Heating also possible without primary air, which saves energy when heating at night and at weekends
    • Heat exchanger cleanable from the top or the bottom (in compliance with requirements of VDI 6022). The large fin spacing enables easy cleaning and obviates the need for a filter.
    • Suitable for new or refurbished buildings

    Service & Downloads

    Your contact person

    Luciana Heim

    International Sales & Business Development

    T +49 241 441 581

    M +49 162 170 2471

    sales@krantz.de